Server rack standards

To help distinguish a rack from a cabinet, consider the rack as the two- or four-post framework to which the IT equipment is secured; either directly or by way of rack rails. The perceived drawbacks with open frame racks illustrates the current trend for enclosed cabinets; that easy access raises security fears due to their susceptibility to damage, either accidental or malicious; that production equipment is exposed to contaminants, dirt and debris; and that exposed cables and cable managers, if poorly maintained, lead to poor aesthetics.
 For the full article from which this summary is paraphrased please visit:        

https://www.anixter.com/en_us/about-us/news-and-events/news/rack-versus-cabinet--which-is-right-for-you-.html

Rack standards

  • Rack enclosures have vendor neutral mounting rails. They are fully adjustable and compatible with all compliant 19” equipment. See Vertiv rack details for further information.

  • Access points for power and data pathways are at the top of the cabinets.

  • Blanking panels will be installed in any unused rack space to minimize cold/hot air mixing.

  • Brushed blanking panels are available for instances requiring front-to-back cable runs:

    Blanking panels

  • Horizontal cable management bars are available:

    Cable management
            
  • Patch cabling is to be contained within each cabinet.
    • Structured fibre cabling is presented within each of the racks
    • Structured Ethernet cabling can be supplied upon request
  • No superfluous items are to be left inside cabinets including, but not limited to:
    • Keyboards
    • Monitors
    • Documents
    • Post-It notes
    • Packaging
    • Fibre Optic cable terminator protectors
    • Tie wraps

Rack Dimensions

  • WCDC:
    • Data Hall 3 - Knurr Racks
      • The space between the front and rear rack strut is 720mm
      • The space between the cabinet edge and the front rack strut is 100mm
      • The space behind the rear rack strut and the cabinet edge is 310mm
      • 47U
    • If the gap is to be extended, to accommodate deeper devices, bear in mind that prescribed cable bend radii need be observed, and that vertical power strips need to be accommodated; these concerns will reduce the theoretical maximum to which the rack depth could be extended.
  • Soulsby Building:
    • SBY-Ax - Rittal Racks
      • The space between the front and rear rack strut is 740mm
      • Scope to extend at front up to 400mm; assuming rack mounted power strips are installed, plus possible loss of vertical cable management tray.
    • SBY-Ex - Unknown brand
      • The space between the front and rear rack strut is 740mm
      • There is no scope to alter the position of the rack struts
  • RNB-MER:
    • The standard MER rack depth is as follows:
      • Between front and rear struts: 730mm
      • Between front strut and front of rack: 75mm
      • Between back strut and back of rack: 180mm